Chemical Pail Installation

Oct 20, 2026

If you understand how the PTLevel measures liquids, then you can effectively install a PTLevel to measure any "liquid" that has a consistent density. Basically, an air pocket is created in the pressure chamber when the pressure chamber is submerged, ...

If you understand how the PTLevel measures liquids, then you can effectively install a PTLevel to measure any "liquid" that has a consistent density. Basically, an air pocket is created in the pressure chamber when the pressure chamber is submerged, that air pocket changes pressure based on the weight of the liquid on it.  Our regular pressure chamber is weighted with Portland (cement), and we want to reduce any contaminants coming in contact with your chemicals, which is why we offer another monitoring solution for chemical pails.

Several chemical pails side by side, each with a tube passing through its lid

We can supply you with a chemical pail adapter kit (instead of a regular pressure chamber) for $15. Please reach out to us directly to place an order for a PTLevel with a chemical pail adapter as these are not currently available on our website. Also please note you will need to supply your own length of 1/2" electrical conduit (purchased from a local hardware store) which needs to be as long as the depth of your tank.

Chemical Pail Adapter Contents:

Parts of the chemical pail adapter labelled A to F: a flat disc, a blue bracket, a grey sleeve, a grey round cap, a white tube and a grey baseChemical Pail Kit

A: Tubing spacer
B: Transmitter Holder
C: Double-sided Cap
D: 2" Flange with universal rubber threads
E: Pressure Chamber
F: Pressure Chamber Base (with 2 tubing connections with check-valves; for suction tubes out of the chemical pail)


Specifications:

Pressure Chamber, cap, and Pressure Chamber Base: PVC
Check Valves Bead: ABS
2" Flange, Spacer: ABS
Rubber threads: TPU
tubing: Polyurethane

Common Chemicals the PTLevel is Resistant To:

1. Chlorine; less than 4% mixture with water
2. Acids; Minimum pH 4
3. Peroxide and HPO4; HPO4 up to 7.5% solution
4. Oils; Food oils like palm, sunflower, soybean, coconut, olive, etc
5, Detergents and Soaps; common liquid soaps, detergents and softeners for industrial laundry businesses, car washes, etc
6. Bases; Maximum pH 10
7. Diesel; The PTLevel is not certified for fuels but our chemical pail parts are resistant to diesel.

Idea
There are no electronic parts required to touch the liquid you are measuring.

Installation Instructions:

Chemical Pail Pressure Chamber Installation: https://youtu.be/CbkuMbEWSjI
Chemical Pail training video: https://youtu.be/ixwWO35PVzY

Step 1: Put together the flange if it did not already come fully assembled.
Hands assembling the gray flange of the pressure chamber, with the pipe and small fittings laid out on a table


Step 2: Put your electrical conduit length through the flange
Step 3: Put your spacer on the conduit
Grey electrical conduit being pushed through the assembled flange, with a spacer and a rubber fitting on the table


Step 4: Optional Transmitter Holder can be placed on top of the conduit
Step 5: Thread your tubing through the conduit
Hands feeding tubing through the top of the assembled gray conduit, with the flange and black spacer on the table


Step 6: Thread the tubing through the double-sided cap (making sure to have the threads in the cap facing out) and push the cap onto the conduit
Hands threading clear tubing through the gray double-sided cap before pushing it onto the white conduit


Step 7: Press the tubing onto the barb of the pressure chamber
Hands pressing the clear tubing onto the grey barb fitting at the end of the grey conduit


Step 8: Thread the pressure chamber onto the cap
Hands threading the white tubing through the double-sided cap on the grey conduit before the pressure chamber is attached


Step 9: Press the Pressure Chamber Base onto the chamber (if it didn't come preassembled)
Hands fitting the grey conduit onto the threaded cap, with white tubing running across the table


Step 10: If wanted, you can install 3/8" suction tubes into your chemical pail. There are 2 check valves within the base.
Hand holding the pressure chamber tube with the white cable running along it, shown on a gray surface


Step 11: Install the pressure chamber into your pail and tighten down the lid. The 2" rubber flange should fit most openings.
Person lowering a PTLevel sensor mounted on a pole into a pink corrosive chemical pail through its lid opening

That's it!

Don't forget to set up your pail depth in Settings and set up Alerts. Enjoy your data!

PTDevices web dashboard Alerts tab showing level alert set points at 40% and 10% with SMS notificationsPTDevices dashboard showing RO Tank at 66% and its Usage History level chart from August 12 to September 8

Pressure chamber tube fitted through the lid of a white chemical pail, with a blue fitting and a green hose beside it

PTLevel sensor mounted on a blue bracket on a chemical pail lid, with a clear tube running into the pail

Several chemical pails side by side, each with a tube passing through its lid

PTLevel DIN Rail Adapter:

(Contact us for pricing and to order DIN Rail adapters for your PTLevels)
Eight PTLevel units mounted vertically on a DIN rail adapter on a wall, with cables and clear tubing connected